Neutral Earthing Resistor For Transformer
CONTENTS
1.Brief Introduction to Product....................................................................................3
2. Applicable Standards...............................................................................................4
3. The Characteristic of the Product............................................................................4
4. Model Instruction.....................................................................................................6
5. Typical Technology Parameters...............................................................................6
6. Schematic Diagram for Wire Connection................................................................7
7. Outline and Installation Dimension.........................................................................9
8. Service Condition...................................................................................................10
9. Notice for Ordering................................................................................................10
10. Cautions of Site Installation.................................................................................11
11. Checking and Testing...........................................................................................12
12. Maintenance.........................................................................................................13
13. Packaging, Transportation and Storage................................................................14
1. Brief Introduction to Product
With neutral grounding resistance is installed, when nonmetal grounding, the current flowing through grounding point and neutral would be much less than that when metal grounding. Meanwhile sound phase voltage rise is lowered a lot and zero-sequence voltage is half of that when single-phase metal grounding. Therefore, adopting neutral grounding via resistance could decrease transient overvoltage when single-phase grounding, and eliminate arc flash hazards like transient overvoltage and some resonant overvoltage, and moreover it could adopt simple relays to quickly locate the fault line and clear it up.
Mingrui has outstanding technical researching team and superior equipments, specially concentrate on research & development, production, sales and service of neutral grounding series products of power distribution system. The transformer neutral grounding resistance we developed and produced is applicable to 6~35KV power distribution grid of cable lines in cities, large industrial enterprises, factories, airports, seaports, subway and etc. as well as 0.66KV system in mine digging and 0.4kv/6kv/10kv system in power plants.
2. Applicable Standards
The design of the product complys with the flowing standards:
DL/780-2001 Neutral Grounding Resistance in Power Distribution
IEC726 Dry-Type Power Transformer
DL/T620-1997 Overvoltage Protection and Insulation Co-ordination of AC
Electrical Equipments
IEC60-1 Experimental Technique of High Voltage
GB1208-1997 Current Transformer
IEC60529:2001 Enclosure Protection Degree (IP code)
IEEE32-1972 Technique Terms and Experiment of Neutral Grounding Device
IEC60081 Insulation Co-ordination of Transmission and Distribution
Device of High Voltage.
DL/T593-1996 Common Specifications for Purchasing High Voltage
Switch Equip